Membran filter with 12 m² membran surface for flow of 1200 l/h special design for legionella protection

automatic backwash governed by time or flow rate with bladder tank 33 L
maximum operating pressure: 5 bar
Process fittings (inlet, filtrate, backwash): 2“ IG
Dimensions (width / height / depth) in mm: 900 / 1700 / 400
Power supply: Schuko Stecker 235 VAC/16A
Power consumption: ca. 200 W
PLC Simatic S7 mit HMI Colour Touch 4"
Pressuresensor 0-10 bar for filtrate and raw water
elektromagnetic flow sensor IDM DN65
Backwash valve as ball valve with elektrical actuator
condensator puffer for fail save of actuator in case of power fail
floot sensor
Enwatmon Datalog
Remote Access via Smart client Siemens